Main
Range
ComPacT
Product name
ComPacT NSX
Device short name
NSX630F
Product or component type
Circuit breaker
Device application
Distribution
Poles description
4P
Protected poles description
4D
3D + N/2
3D
Neutral position
Left
[In] rated current
630 A at 40 °C
[Ue] rated operational voltage
690 V AC 50/60 Hz
Network type
AC
Network frequency
50/60 Hz
Suitability for isolation
Yes conforming to EN/IEC 60947-2
Utilisation category
Category A
Breaking capacity
40 kA Icu at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
36 kA Icu at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
30 kA Icu at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA Icu at 500 V AC 50/60 Hz conforming to IEC 60947-2
20 kA Icu at 525 V AC 50/60 Hz conforming to IEC 60947-2
10 kA Icu at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
85 kA Icu at 240 V AC 50/60 Hz conforming to UL 60947-4-1
35 kA Icu at 480 V AC 50/60 Hz conforming to UL 60947-4-1
20 kA Icu at 600 V AC 50/60 Hz conforming to UL 60947-4-1
Breaking capacity code
F 36 kA 415 V AC
Trip unit name
MicroLogic 2.3
Trip unit technology
Electronic
Trip unit protection functions
LSoI
Control type
Toggle
Circuit breaker mounting mode
Fixed
Complementary
[Ui] rated insulation voltage
800 V AC 50/60 Hz
[Uimp] rated impulse withstand voltage
8 kV
[Ics] rated service breaking capacity
40 kA at 220/240 V AC 50/60 Hz conforming to IEC 60947-2
36 kA at 380/415 V AC 50/60 Hz conforming to IEC 60947-2
30 kA at 440 V AC 50/60 Hz conforming to IEC 60947-2
25 kA at 500 V AC 50/60 Hz conforming to IEC 60947-2
10 kA at 525 V AC 50/60 Hz conforming to IEC 60947-2
10 kA at 660/690 V AC 50/60 Hz conforming to IEC 60947-2
Mechanical durability
15000 cycles
Electrical durability
8000 cycles at 440 V In/2
4000 cycles at 440 V In
6000 cycles at 690 V In/2
2000 cycles at 690 V In
Power dissipation per pole
39.7 W
Mounting support
Backplate
Mounting position
Horizontal and vertical
Flat on the back
Upside connection
Front
Downside connection
Front
Connection pitch
45 mm
Protection type
L : for overload protection (long time)
So : for short time short-circuit protection with fixed delay
I : for instantaneous short-circuit protection
Trip unit rating
630 A at 40 °C
Long-time pick-up adjustment type Ir (thermal protection)
Adjustable 9 settings
[Ir] long-time protection pick-up adjustment range
250…630 A
Long-time protection delay adjustment type tr
Fixed
[tr] long-time delay adjustment range
400 s at 1.5 x Ir
16 s at 6 x Ir
11 s at 7.2 x Ir
Neutral protection setting
0.5 x Ir (3D + N/2)
1 x Ir (4D)
No protection (3D)
Thermal memory
20 minutes before and after tripping
Short-time protection pick-up adjustment type Isd
Adjustable 9 settings
[Isd] Short-time protection pick-up adjustment range
1.5…10 x Ir
Short-time protection delay adjustment type tsd
Fixed
Instantaneous protection pick-up adjustment type Ii
Fixed
[Ii] instantaneous protection pick-up adjustment range
6900 A
Earth-leakage protection
Without
Zone selective interlocking ZSI
Without
Number of slots
6 slot(s)
Local signalling
Flashing LED (green) for ready to operate
LED 105 % Ir (red) for overload
LED 90 % Ir (orange) for overload
Width (W)
185 mm
Height (H)
255 mm
Depth (D)
110 mm
Net weight
8.13 kg
Environment
Standards
EN/IEC 60947-2
Overvoltage category
III
Electrical shock protection class
Class II on front face
Pollution degree
3 conforming to IEC 60664-1
IP degree of protection
IP40 conforming to IEC 60529
IK degree of protection
IK07 conforming to IEC 62262
Ambient air temperature for operation
-25…70 °C
Ambient air temperature for storage
-50…85 °C
Relative humidity
0…95 %
Operating altitude
0…2000 m without derating
2000 m…5000 m with derating

Berat8,2 kg
Dimensi12 × 20 × 26 cm
Brand

SCHNEIDER

Cek Ongkir


Keranjang saya
Wishlist
Baru Dilihat
Kategori
Bandingkan Produk (0 Produk)